Installation Details Of Anti-static Elastic Floor
Jun 21, 2019
Leave a message
The room design technical performance of anti-static elastic floor mainly refers to its mechanical and electrical performance. The mechanical performance mainly considers its bearing capacity and wear resistance.
When the whole anti-static elastic floor is installed on the overlapped truss beam, the load-bearing capacity of the anti-static elastic floor should be more than 1000kg/m2 after placing the anti-static elastic floor horizontally; the concentrated load of any part of the anti-static elastic floor should be more than 300kg, and the deflection should be less than 2mm when the load-bearing point with diameter of 6cm is 300kg, and there is no permanent deformation.
The load of the anti-static elastic floor should be determined based on the weight of the heaviest equipment in the machine room, so as to prevent the permanent deformation or damage of the elastic floor caused by the overweight of some equipment.