Introduction Of SPC Floor Installation Process
Jul 01, 2019
Leave a message
The first step of SPC floor installation: Ground detection, temperature and humidity detection by thermohygrometer, indoor temperature and surface temperature should be 15 C, and should not be constructed below 5 C or above 30 C. The relative air humidity suitable for construction should be between 20% and 75%. The moisture content of the grass-roots should be less than 3% when the moisture content of the grass-roots is measured by the moisture content tester. The strength of base should not be lower than that of concrete C-20. Otherwise, proper self-leveling should be adopted to strengthen the strength. The surface hardness of the base should not be less than 1.2 MPa by hardness tester. For the construction of stone-plastic floor materials, the unevenness of the base should be less than 2 mm in the range of 2 meters. Otherwise, appropriate self-leveling should be adopted to leveling.